POWER CABLES

Power cables low voltage with PVC insulation


«back

СВТ

NYCY

Standard: VDE 0276 part 603

Description:

Cu conductors • PVC insulation • Cu concentric conductor • PVC sheath

Application:

NYCY is used in power plants, industrial and switching installations, for street lighting, domestic power supply connections, in secondary distribution networks and other.These cables are preferentially used for underground application as well as for interior installation in room and cableducts and for outdoor and applications, for indoor installations, in the open air, underground and in water where greater mechanical protection an protection against accidental contact is required if damaged.
Note
Other core configuration and special constructions manufactured upon request.

Characteristics:


Color coding:


Single core Doube core 3 – core 4 - core
black blue and brown brown black grey blue brown, black grey

Cable construction

Technical data

Construction According to VDE 0276 part 603 Conductor resistance at 20° C According to VDE 0295
class 1 or 2 (IEC 60228)
Conductor solid or multi-strand Cu wires class 1 or 2 acc. VDE 0295 (IEC 60228) Max. conductor temperature +70° C
Insulation PVC type DIV4 acc. VDE0276 Max. short circuit temperature +160° C , not more than 5 sec
Core identification according to VDE 0293 Rated voltage Uo/U 0.6/1 kV
Inner sheath tapes and filling compound Test voltage AC – 4 kV     50 Hz
Sheath PVC type DMV5 acc. VDE 0276 Bending radius
-single core
-multi core


15 cable diameter
12 cable diameter
Color black Flame test VDE 0472 part 804 class B
(IEC 332 part 1)

 Construction data NYCY 0.6/1 kV