Standart: IEC 60502,VDE 0276/604

Description: Cu / Al conductors • XLPE insulation • Armour-st. tapes • LSF sheaths

Application:

The power cables flame retardant, with low halogen free smoke emission and corrosion at fire conditions are suitable for use in electrical installations for nominal voltage 0.6/1kV in: -important objects - power stations (nuclear, thermal), transformer substations, metro, airport, -public buildings - hospitals, hotels, theaters, cinemas, public and commercial centers, -places with great concentration of people and material values whose safety in case of fire should be    guaranteed. The cables can be laid indoor, in air or in concrete. Direct laying underground or in water is not allowed.

Features:

Color coding:

 

Single core Doube core 3 – core 4 - core 5 - core Multiple core
black or yellow/green blue and brown or yellow-green and black brown, black grey or yellow/green blue, brown blue, brown, black, grey or yellow/green, brown, black, grey blue, brown, black, grey, black or yellow/green, blue, brown, black, grey black with number mark on cores or black with number mark on cores and yellow/green core in the outer cover.

 

 

 

Cable construction

Technical data

Construction According to IEC 60502-1 Conductor resistance According to IEC 60228
Operating temperature 90° C
Conductor Cu solid or stranded wires class 1 or 2 according to IEC 60228 Overload temperature 130° C/100h per year
Short circuit temperature 250° C ( 5 sec.)
Insulation XLPE compound Nominal voltage 0.6/1 kV
Highest system voltage 1.2 kV
Identification of cores color code acc.
to VDE 0276-604
Test voltage, AC 50 Hz 4.0 kV
Bending radius
-single core
-multicore

15 x Dcable
15 x Dcable
Inner sheath halogen free compound Temperature of laying no less than 0° C
Armour two steel tapes or two galvanized steel tapes Temperature of exploitation -30 to 70° C
Sheath halogen free compound , flame retardant Tests
-flame retardant
-corrosivity of combustion gases and conductivity
pH - min 4.3; σ-max100μS/cm
-density of smoke gases
IEC 60502-1 and VDE 0276-604
VDE 0472 p804/ С ( IEC 332-3/С and В)
VDE 0472p813 (IEC 60754-1and2)
VDE 0472p816 (IEC 61034- 1and2)
Color black