Standart: IEC 60502,VDE 0276/604
Description: Cu / Al conductors • XLPE insulation • Armour-st. tapes • LSF sheaths
The power cables flame retardant, with low halogen free smoke emission and corrosion at fire conditions are suitable for use in electrical installations for nominal voltage 0.6/1kV in: -important objects - power stations (nuclear, thermal), transformer substations, metro, airport, -public buildings - hospitals, hotels, theaters, cinemas, public and commercial centers, -places with great concentration of people and material values whose safety in case of fire should be guaranteed. The cables can be laid indoor, in air or in concrete. Direct laying underground or in water is not allowed.
Color coding:
| Single core | Doube core | 3 – core | 4 - core | 5 - core | Multiple core |
| black or yellow/green | blue and brown or yellow-green and black | brown, black grey or yellow/green blue, brown | blue, brown, black, grey or yellow/green, brown, black, grey | blue, brown, black, grey, black or yellow/green, blue, brown, black, grey | black with number mark on cores or black with number mark on cores and yellow/green core in the outer cover. |
|
Cable construction |
Technical data |
||
| Construction | According to IEC 60502-1 | Conductor resistance | According to IEC 60228 |
| Operating temperature | 90° C | ||
| Conductor | Cu solid or stranded wires class 1 or 2 according to IEC 60228 | Overload temperature | 130° C/100h per year |
| Short circuit temperature | 250° C ( 5 sec.) | ||
| Insulation | XLPE compound | Nominal voltage | 0.6/1 kV |
| Highest system voltage | 1.2 kV | ||
| Identification of cores | color code acc. to VDE 0276-604 |
Test voltage, AC 50 Hz | 4.0 kV |
| Bending radius -single core -multicore |
15 x Dcable 15 x Dcable |
||
| Inner sheath | halogen free compound | Temperature of laying | no less than 0° C |
| Armour | two steel tapes or two galvanized steel tapes | Temperature of exploitation | -30 to 70° C |
| Sheath | halogen free compound , flame retardant | Tests -flame retardant -corrosivity of combustion gases and conductivity pH - min 4.3; σ-max100μS/cm -density of smoke gases |
IEC 60502-1 and VDE 0276-604 VDE 0472 p804/ С ( IEC 332-3/С and В) VDE 0472p813 (IEC 60754-1and2) VDE 0472p816 (IEC 61034- 1and2) |
| Color | black | ||