Standart: IEC 60502-2, VDE 0276-620
Description: Cu / Al conductors • XLPE insulation • Cu screen • PЕ sheath
The three-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20; 18/30 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer’s substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.
|
Cable construction |
Technical data |
||
| Construction | According to IEC 60502 and DIN VDE 0276-620 | Conductor resistance | According to BDS904 (IEC60228) class 2 and VDE 0295 class 2 |
| Conductor | Сu and Al stranded compacted, according to IEC 60228 class 2 and VDE 0295 class 2 | Operating temperature | 90° C continuous operation |
| Short circuit temperature | 250° C ( 5 sec.) | ||
| Inner semi- conductive layer | semi-conductive XLPE compound | Overload temperature | 130° C /100h per year max./ |
| Insulation | XLPE compound | ||
| Outer semi- conductive layer | semi-conductive XLPE compound and semi-conductive tape or extruded semi-conductive XLPE compound | Nominal voltage Uo/U | 6/10; 12/20; 18/30 kV |
| Highest system voltage Uo/U, no more than | 6/10; 12/20; 18/30 kV 12kV; 24kV; 36kV |
||
| Test voltage AC (») - 5 min DC (=) - 15 min |
6/10; 12/20; 18/30kV 21kV; 42kV; 63kV 67kV; 134kV; 201kV |
||
| Metal screen | Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm or Cu tapes laid with overlap over each phase | Bending radius | 15 x Dcable |
| Level of partial discharge at 2*Uo | max. 5 pC / 2 pC | ||
| Cable assembly | Three insulated and screened phases are twisted with fillings and tape support | Temperature of laying | no less than -5° C |
| Inner sheath | PVC compound | Temperature of exploitation | -30° C to 50° C |
| Sheath | PE compound | Tests | according to IEC 60502-2 or DIN VDE 0276-620 |
| Color | Black | Force of strain in laying N max. | Al cores - 30*n*S core Cu cores - 50*n*S core, -n-number of cores and -S-nominal cross section of cores in mm |
Other products in this category Back to all products
-
2XSY / N2XSY / A2XSY / NA2XSY
-
2XS2Y / N2XS2Y / A2XS2Y / NA2XS2Y
-
2XS(F)2Y / N2XS(F)2Y / A2XS(F)2Y / NA2XS(F)2Y
-
2XS(F)2Y / N2XS(F)2Y / A2XS(F)2Y / NA2XS(F)2Y-Triplex
-
2XS(FL)2Y / N2XS(FL)2Y / A2XS(FL)2Y / NA2XS(FL)2Y
-
2XSEY / N2XSEY / A2XSEY / NA2XSEY
-
2XSE2Y / N2XSE2Y / A2XSE2Y / NA2XSE2Y
-
2XSE(F)2Y / N2XSE(F)2Y / A2XSE(F)2Y / NA2XSE(F)2Y
-
2XSEYBY / A2XSEYBY
-
2XS2Y / N2XS2Y / A2XS2Y / NA2XS2Y - Triplex