Standart: IEC 60502, VDE 0276/620
Description: Cu or Al conductors • XLPE insulation • Cu screen • Al foil • PE sheath
The three single-core cables with insulation of cross-linked polyethylene (XLPE) factory bindled in TRIPLEX, are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20; 18/30 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer’s substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.
|
Cable construction |
Technical data |
||
| Construction | According to IEC 60502 and DIN VDE 0276-620 | Conductor resistance | According to IEC60228 class 2 and VDE 0295 class 2 |
| Conductor | Сu and Al stranded compacted, according to IEC 60228 class 2 and VDE 0295 class 2 | Operating temperature | 90° C continuous operation |
| Short circuit temperature | 250° C ( 5 sec.) | ||
| Inner semi- conductive layer | semi-conductive XLPE compound | Overload temperature | 130° C /100h per year max./ |
| Insulation | XLPE compound | ||
| Outer semi- conductive layer | semi-conductive XLPE compound | Nominal voltage Uo/U | 6/10; 12/20 kV |
| Highest system voltage Uo/U, no more than | 6/10; 12/20 kV 12; 24 kV; |
||
| Test voltage AC (») - 5 min DC (=) - 15 min |
6/10; 12/20 kV 21; 42kV 67; 134kV |
||
| Water resisting element | Layer of semi-conductive water absorbing tapes | Bending radius | 15 x Dcable |
| Level of partial discharge at 2*Uo | max. 5 pC / 2 pC | ||
| Metal screen | Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. | Temperature of laying | no less than -20° C |
| Water resisting element | – water absorbing powder | Temperature of exploitation | -30° C to 50° C |
| Radial protection from moisture ingress | Al foil with copolymer layer | Tests | according to IEC 60502-2 or DIN VDE 0276-620 |
| Sheath | PE compound | Force of strain in laying N max. | Al cores - 30*n*S core Cu cores - 50*n*S core, -n-number of cores and -S-nominal cross section of cores in mm |
| Color | black | ||
| Factory bundled in TRIPLEX | three single-core cables factory bindled in TRIPLEX | Tests – water penetration in the region of metallic screen | IEC 60502-2 annex F |
| Sheath | PE compound | ||
| Color | black | ||
Other products in this category Back to all products
-
2XSY / N2XSY / A2XSY / NA2XSY
-
2XS2Y / N2XS2Y / A2XS2Y / NA2XS2Y
-
2XS(F)2Y / N2XS(F)2Y / A2XS(F)2Y / NA2XS(F)2Y
-
2XS(F)2Y / N2XS(F)2Y / A2XS(F)2Y / NA2XS(F)2Y-Triplex
-
2XS(FL)2Y / N2XS(FL)2Y / A2XS(FL)2Y / NA2XS(FL)2Y
-
2XSEY / N2XSEY / A2XSEY / NA2XSEY
-
2XSE2Y / N2XSE2Y / A2XSE2Y / NA2XSE2Y
-
2XSE(F)2Y / N2XSE(F)2Y / A2XSE(F)2Y / NA2XSE(F)2Y
-
2XSEYBY / A2XSEYBY
-
2XS2Y / N2XS2Y / A2XS2Y / NA2XS2Y - Triplex