Standart: IEC 60 502-1

Description: Cu/Al conductors • XLPE insulation • PVC inner sheath • Armour St. wires • PVC sheath

Application:

These cables are designed for transfer and distribution of electrical power with nominal voltage U 0 / U 0 6/1 kV, frequency 50Hz and surroundings, which require non-proliferation of flames. 2XYRYfr and A2XYRYfr is used in power plants, industrial and switching installations, for street lighting, domestic power supply connections, in secondary distribution networks and other.These cables are preferentially used for underground application as well as for interior installation in room and cableducts and for outdoor and applications, for indoor installations, where greater mechanical protection an protection against accidental contact is required if damaged.

Features:

 

 

Cable construction

Technical data

Construction According to IEC 60502-1 Conductor resistance   at  20° C According class 1 or 2
IEC 60228
Conductor solid or multi-strand Al or Cu  wires class 1 or 2 acc. IEC 60228 Max. conductor temperature 90° C continuous operation
Insulation XLPE compaund Overload temperature 130° C /100h/per year мах./
Color Double core -light blue and brow or yellow-green and black
3 – core – brown, black, grey or yellow/green, light blue, brown
4 – core light blue, brown, black, grey or yellow/green, brown, black, grey
5 – core light blue, brown, black, grey black or yellow/green, light blue, brown black, grey
Multiple core - Black with numbered pair in each cover
Short circuit temperature 250° C /5 s max./
Nominal voltage Uo/U 0.6/1 kV
Highest system voltage 1.2 kV
Inner sheath PVC flame retardant, degree of flame retardancy Test voltage AC – 5 min. between cores - 3.5 кV
between core and screen –
3.5  кV
Bending radius, min.   15x D cable
Armour galvanized iron wires twisted concentrically Temperature of laying no less than 0° C
Sheath PVC flame retardant, degree of flame retardancy Temperature of exploitation 30 to 50° C
Color Black Flame retardancy IEC 60 332-3
Category A