Standart: IEC 60840/IEC 60502
Description: Al cores • XLPE insulation • Cu screen • PVC sheath
The cables are for power supply of electrostatic filters to 111 kV. Conditions for laying - underground, in premises, in cable ducts and conduits and outdoor under shelter.
|
Technical data |
Technical data |
||
| Construction | According to IEC, VDE | Aluminium current core - circular multiwire compacted - nominal cross-section - diameter |
mm² 50 mm 8.2 |
| Conductors | Al stranded compacted, wires according to IEC 60228 cl.2 VDE 0295 cl..2 | Insulation thickness | mm 11.0 |
| Sheath thickness | mm 2.5 | ||
| Inner semi- conductive layer | semi-conductive XLPE compound | Metal screen cross-section | mm² 16 |
| Outer diameter approx. | mm 40.0 | ||
| Insulation | XLPE compound | Mass of core | kg/km 131 |
| Mass of cable | kg/km 1524 | ||
| Outer semi- conductive layer | semi conductive XLPE compound | Bending radius single bending |
m 0.65 сm min 60 |
| Metal screen | Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm | Electrical resistance of core at DC and 20oC | Ω/km 0.641 |
| Electrical resistance of screen at DC and 20oC | Ω/km 1.15 | ||
| Separating layer | layer of plastic tape | Electrical resistance of insulation | MΩ.km 1*105 |
| Operating capacitance | µF/km 0.11 | ||
| Sheath | PVC compound | Maximum allowed ambiend temperature | 90° C |
| Test voltage /15 min/ AC voltage DC voltage |
kV 111 kV 333 |
||
| Color | red | Partial discharge at U=50 kV - max | pC 10 |
| Dielecttric loss / tg β /, мах. Increase of tg β /Δtg β/ U between 15–38 kV U between 38–89 kV |
30.104 10.104 10.104 |
||