Interested in this product?

Send us a request and we will contact you

Our Certificates

Standart: IEC 60840/IEC 60502

Description: Al cores • XLPE insulation • Cu screen • PVC sheath

Application:

The cables are for power supply of electrostatic filters to 111 kV. Conditions for laying - underground, in premises, in cable ducts and conduits and outdoor under shelter.

Features:

 

 

Technical data

Technical data

Construction According to IEC, VDE Aluminium current core
- circular multiwire compacted
- nominal cross-section
- diameter
mm² 50
mm 8.2
Conductors Al stranded compacted, wires according to IEC 60228 cl.2 VDE 0295 cl..2 Insulation thickness mm  11.0
Sheath thickness mm 2.5
Inner semi- conductive layer semi-conductive XLPE compound Metal screen cross-section mm²   16
Outer diameter approx. mm 40.0
Insulation XLPE compound Mass of core kg/km  131
Mass of cable kg/km 1524  
Outer semi- conductive layer semi conductive XLPE compound Bending radius
single bending
m    0.65
сm  min 60
Metal screen Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm Electrical resistance of core at DC and 20oC Ω/km 0.641
Electrical resistance of screen at DC and 20oC Ω/km 1.15
Separating layer layer of plastic tape Electrical resistance of insulation                
MΩ.km    1*105
Operating capacitance µF/km 0.11
Sheath PVC compound Maximum allowed ambiend temperature  90° C
Test voltage /15 min/
AC voltage
DC voltage
kV 111
kV 333
Color red Partial discharge at U=50 kV - max pC 10
Dielecttric loss / tg β /, мах.
Increase of tg β /Δtg β/
U between 15–38 kV
U between 38–89 kV
30.104

10.104
10.104