Interested in this product?

Send us a request and we will contact you

Our Certificates

Standart: BS 5467-1997

Description: Cu conductors • XLPE insulation • PVC sheath • St wire armour • PVC sheath

Application:

The power and control cables with cross-linked polyethylene (XLPE) armored with galvanized steel wires are used in electrical installations with nominal voltage Uo/U 0.6/1 kV. These cables are used in industrial installations and urban networks. These cables are for fixed assembly in lines with unlimited difference levels, for laying in industrial installations, in cable ducts, tunnels and conduits, over shelves and grilles outdoor under shelters.

Features:

 

 

Cable construction

Technical data

Construction According to BS 5467-97 Conductor resistance According to BS 6360 (IEC228) class 2
Conductor Сu wires stranded according to BS 6360 ( IEC 60228 ) class 2 Operating temperature +90° C
Short circuit temperature 250° C ( 5 sec.)
Insulation XLPE compound Overload temperature 130° C/100h per year
Colors 2-cores - brown; blue
3-cores - brown; black; grey
4-cores – brown; black; grey; blue
5-cores – brown; black; grey; green /yellow; blue
Control – black with white numbers or white with black numbers
Nominal voltage Uo/U 0.6/1 kV
Highest system voltage 1.2 kV
Test voltage between cores - 3.5 кV between core and screen - 3.5 кV   
Inner sheath polymer compound Bending radius
- circular cores
- sector

6 x Dcable
8 x Dcable
Armour galvanized steel wires , applied helically Temperature of laying no less than 0° C
Sheath PVC compound Temperature of exploitation -30° C to 50° C
Color black Force of strain in laying N max. Cu cores - 50*n*S core,
-n-number of cores and -S-nominal cross section of cores in mm