Standart: HD 603 S1 part 3А
Description: Al conductors • PVC insulation • PE sheath
E-AY2Y is used in power plants industrial and switching installations, in secondary distribution networks and other.These cables are preferentially used in outdoor applications, for indoor instalations, in the open air, underground and in water where mechanical damage is not anticipated. Note Other core configuration and special constructions manufactured upon request. Cables with same construction may produced according to IEC 60502.
Color coding:
| Single core | Doube core | 3 – core | 4 - core | 5 - core |
| black or yellow/green | blue and brown or yellow-green and black | brown, black, grey or yellow/green, blue, brown | blue, brown, black, grey or yellow/green, brown, black, grey | blue, brown, black, grey, black or yellow/green, blue, brown, black, grey |
|
Cable construction |
Technical data |
||
| Construction | According to VDE 0276 part 603 | Conductor resistance at 20° C | According to VDE 0295 class 1 or 2 (IEC 60228) |
| Conductor | solid or multi-strand Al wires class 1 or 2 acc. VDE 0295 (IEC 60228) | Max. conductor temperature | +70° C |
| Insulation | PVC compound | Max. short circuit temperature | +160° C , not more than 5 sec |
| Core identification | according to VDE 0293 | Rated voltage Uo/U | 0.6/1 kV |
| Test voltage | AC – 4 kV 50 Hz | ||
| Sheath | PE compound | Bending radius -single core -multi core |
15 cable diameter 12 cable diameter |
| Color | black | ||