Standart: NBN C 33-323
Description: Cu / Al conductors • XLPE insulation • Cu screen • PVC sheath
The single-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal water-blocking elements, are designed for transfer and distribution of electrical power with nominal voltage Uo/U U 8.7/15kV , 12/20kV, и 20.8/36 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer’s substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.
|
Cable construction |
Technical data |
||
| Construction | According to NBN C 33-323 | Conductor resistance | According to IEC60228 class 2 (NBN C 30-228) |
| Conductor | Сu and Al stranded compacted, according to IEC 60228-2 (NBN C 30-228 | Operating temperature | 90° C continuous operation |
| Short circuit temperature | 250° C ( 5 sec.) | ||
| Inner semi- conductive layer | semi-conductive XLPE compound | Overload temperature | 120° C /100h per year max./ |
| Insulation | XLPE compound | ||
| Outer semi- conductive layer | semi-conductive XLPE compound | Nominal voltage Uo/U | 8.7/15; 12/20; 20,8/36 kV |
| Highest system voltage Uo/U, no more than | 8.7/15; 12/20; 20.8/36 kV 17.5 kV; 24 kV; 41.5kV |
||
| Water resisting element | Layer of semi-conductive water absorbing tapes | Test voltage AC (») - 5 min |
8.7/15; 12/20; 20.8/36 kV 35 kV; 48 kV; 83 kV |
| Metal screen | Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. | Bending radius | 15 x Dcable |
| Water resisting element | water absorbing insulating tape | Level of partial discharge at 2*Uo | max. 5 pC |
| Sheath | PVC compound | Temperature of laying | no less than -15° C |
| Color | Red | Temperature of exploitation | -30° C to 50° C |
| Tests | according to NBN C 33 323 | ||
| Force of strain in laying N max | Al cores - 30*n*S core Cu cores - 50*n*S core where N is number of cores and S is cross section of cores in mm |
||
Other products in this category Back to all products
-
2XSY / N2XSY / A2XSY / NA2XSY
-
2XS2Y / N2XS2Y / A2XS2Y / NA2XS2Y
-
2XS(F)2Y / N2XS(F)2Y / A2XS(F)2Y / NA2XS(F)2Y
-
2XS(F)2Y / N2XS(F)2Y / A2XS(F)2Y / NA2XS(F)2Y-Triplex
-
2XS(FL)2Y / N2XS(FL)2Y / A2XS(FL)2Y / NA2XS(FL)2Y
-
2XSEY / N2XSEY / A2XSEY / NA2XSEY
-
2XSE2Y / N2XSE2Y / A2XSE2Y / NA2XSE2Y
-
2XSE(F)2Y / N2XSE(F)2Y / A2XSE(F)2Y / NA2XSE(F)2Y
-
2XSEYBY / A2XSEYBY
-
2XS2Y / N2XS2Y / A2XS2Y / NA2XS2Y - Triplex