Standart: BDS HD 21.3 S3, VDE 0281-3
Description: Cu conductors • PVC insulation
H07V-U/-R/-K PVC-insulated single-core cable according to VDE 0281 part 3,HD 21.3 S3 and IEC 227-3. These PVC-insulated single-core cables are used for the internal wiring of equipment switching systems and distributors as well as for the protected installation in and to lighting fixtures with a rated voltage up to 1000 V alternating current or a direct voltage up to 750 V, earthed. These cables are suitable for installation in dry rooms, switching and distribution systems, in conduit, on, in and under plaster as well as in closed installation ducts. Note (for H07V) These single-core cables may not be used for direct installation on flatbed bodies, ducts or tanks. Approved for use as potential-compensating cable directly on, in and underneath plaster as well as on flatbed bodies or similar.
|
Description |
Technical data |
||
| Conductor | copper wires,according to VDE 0295 class 1,2 or 5 (IEC 60228) | Conductor resistance at 20° C | according to VDE 0295 and IEC 60228 |
| Core temperature, max | 70° C in operation | ||
| Insulation | PVC compound | Rated voltage Uo/U | 450/750 V |
| Test voltage AC, 50 Hz: | 2500 V | ||
| Color | black, red, blue, pink, gray, yellow, green, brown, white, violet, orange Two-color combinations are not permitted except for green/yellow. |
Temperature range mobile: fixed : |
- 5 ° C to + 70° C - 30° C to + 70° C |
| Bending radius up to 10 mm diameter >10 mm diameter |
10 x cable diameter 15 x cable diameter |
||
| Flame test | test class B according To VDE 0472part 804 and IEC 60 332-1 | ||