Standart: VDE 0276/604
Description: Cu conductors • XLPE insulation • LSF sheaths
The power cables flame retardant, with low halogen free smoke emission and corrosion at fire conditions are suitable for use in electrical installations for nominal voltage 0.6/1kV in: -important objects - power stations (nuclear, thermal), transformer substations, metro, airport, -public buildings - hospitals, hotels, theaters, cinemas, public and commercial centers, -places with great concentration of people and material values whose safety in case of fire should be guaranteed. The cables can be laid indoor, in air or in concrete. Direct laying underground or in water is not allowed.
Color coding:
| Single core | Doube core | 3 – core | 4 - core | 5 - core | Multiple core |
| black or yellow/green | blue and brown or yellow-green and black | brown, black grey or yellow/green blue, brown | blue, brown, black, grey or yellow/green, brown, black, grey | blue, brown, black, grey, black or yellow/green, blue, brown, black, grey | black with number mark on cores or black with number mark on cores and yellow/green core in the outer cover. |
|
Cable construction |
Technical data |
||
| Construction | According to VDE 0276-604 | Conductor resistance at 20° C | according to VDE 0295 (IEC60228) class 1 or 2 |
| Conductor | Сu wires according to VDE 0295 (HD 383) cl.1 or 2 (IEC 60228) | ||
| Insulation | XLPE compound | Operating temperature | 90° C continuous operation |
| Overload temperature | 130° C /100h per year max/ | ||
| Core identification | according to VDE 0250 and VDE 0293 |
Short circuit temperature | 250° C / 5 s max./ |
| Inner sheath | halogen free compound | Nominal voltage Uo/U: | 0.6/1 kV |
| Test voltage, АC - 5 min | between cores - 3.5 кV | ||
| Bending radius, min | 6xD cable | ||
| Highest system voltage | no more than 1.2 kV | ||
| Sheath | halogen free compound, flame retardant | Temperature of laying | no less than 0° C |
| Temperature of exploitation | -30 to 50° C | ||
| Color | black | Tests flame retardancy -corrosivity of combustion gases pH - min 4.3; σ-max100μS/cm -density of smoke gases |
VDE 0276-604 VDE 0472 p804/ С ( IEC 332-3/С and В) VDE 0472p813 (IEC 60754- 1and 2) VDE 0472p816 (IEC 61034-1and 2) |