Interested in this product?

Send us a request and we will contact you

Our Certificates

Standart: VDE 0250/214

Description: Cu conductors • XLPE insulation • LSF sheaths

Application:

The power insulated conductors flame retardant, with low halogen free smoke emission and corrosion at fire conditions are suitable for use in electrical installations for Uo/U 300/500 V in: - important objects - power stations (nuclear, thermal), transformer substations, metro, airport, - public buildings - hospitals, hotels, theaters, cinemas, public and commercial centers, - places with great concentration of people and material values whose safety in case of fire should be guaranteed. The conductors are designed for laying over, in and under plasters in dry and wet premises as well as in brickwork”s and concrete. They are also suitable for outdoor use. The conductors should not be laid directly in vibro concrete or rammed concrete and directly under ground.

Features:

Color coding:

 

Single core Doube core 3 – core 4 - core 5 - core Multiple core
black or yellow/green blue and brown or yellow-green and black brown, black grey or yellow/green blue, brown blue, brown, black, grey or yellow/green, brown, black, grey blue, brown, black, grey, black or yellow/green, blue, brown, black, grey black with number mark on cores or black with number mark on cores and yellow/green core in the outer cover.

 

 

 

Cable construction

Technical data

Construction According to VDE 0250-214 Conductor resistance at 20° C according to  VDE 0295 (IEC60228) class 1 or 2
Conductor Сu wires according to VDE 0295 (HD 383) cl.1 or 2 (IEC 60228)
Insulation XLPE compound Operating temperature 70° C
Core identification according to VDE 0250
and VDE 0293
Short circuit temperature 160° C / 5 sec max./
Inner sheath halogen free compound Nominal voltage Uo/U: 300/500 V
Test voltage АС - 2kV
Bending radius, min 4xD cable
Sheath halogen free compound, flame retardant Tests
flame retardancy
-corrosivity of combustion gases
pH - min 4.3;
σ-max100ΩS/cm
-density of smoke gases
DIN VDE 0250-214
VDE 0472 ч804/ С( IEC 332-3/СandВ)
VDE 0472ч813 (IEC 60754-1и2)
VDE 0472ч816 (IEC 61034-1и2)
Color grey RAL 7035