Standart: VDE 0276 part 627
Description: Cu conductors • PVC insulation • Cu concentric conductor • PVC sheath
NYCY is used in power plants, industrial and switching installations, for street lighting, domestic power supply connections, in secondary distribution networks and other.These cables are also used as control cables for transmission of measured values control and regulation pulses.These cables are preferentially used for underground application as well as for interior installation in room and cableducts and for outdoor and applications, for indoor installations, in the open air, underground and in water where greater mechanical protection an protection against accidental contact is required if damaged. Note Other core configuration and special constructions manufactured upon request. Cables with same construction may produced according to IEC 60502
Color coding
- Black with number mark on cores or black with number mark on cores and yellow/green in the outer cover
|
Cable construction |
Technical data |
||
| Construction | According to VDE 0276 part 603 | Conductor resistance at 20° C | According to VDE 0295 class 1 or 2 (IEC 60228) |
| Conductor | solid or multi-strand Cu wires class 1 or 2 acc. VDE 0295 (IEC 60228) | Max. conductor temperature | +70° C |
| Insulation | PVC type DIV4 acc. VDE0276 | Max. short circuit temperature | +160° C , not more than 5 sec |
| Core identification | according to VDE 0293 | Rated voltage Uo/U | 0.6/1 kV |
| Inner sheath | tapes and filling compound | Test voltage | AC – 4 kV 50 Hz |
| Concentric conductor | of plain round copper wires and one or two transverse counter helix of copper tapes | ||
| Sheath | PVC type DMV5 acc. VDE 0276 | Bending radius -single core -multi core |
15 cable diameter 12 cable diameter |
| Color | black | Flame test | VDE 0472 part 804 class B (IEC 332 part 1) |