Interested in this product?

Send us a request and we will contact you

Our Certificates

Standart: BS 6346

Description: PVC insulation • wires stranded in layers • wraping • PVC bedding • armour • sheath of PVC

Application:

These cables are preferentially used in outdoor applications, for indoor instalations, in the open air, underground and in water where mechanical damage is anticipated.

Features:
Identification of cable wires
Number of wires a-wire Number of wires a-wire Number of wires a-wire
1 brown 8 orange 15 grey/red
2 yellow 9 red/white 16 black/red
3 green 10 grey 17 violet/red
4 red 11 red/blue 18 orange/red
5 white 12 violet 19 green/red
6 blue 13 brown/red 20 blue/ white
7 black 14 yellow/red    

Core identification for 4x1(1.5) – red-blue-yellow-green.

 

 

Description

Technical data

Conductor solid copper conductor
to BS 6360
Cross sectionin mm2 : 1.0       1.5
Conductor
size
1.00mm2 =1/1.13mm
1.50mm2 =1/1.38mm
Cond.resistance at 20° C max.:Ω/km 18.1      12.1
Insulation:
-material
-radial thickness,nom

PVC type TI1 complying to BS 7655
0.6mm
Insulation resistance min. MΩ.km 100       100
Cable core the wires are stranded into layers Mutual capacitance at 800Hz. max.nF/km 120       140
Wrapping minimum of 1 layer of plastic tape Voltage rating 600/1000 V
Inner Sheath PVC compound type TM1 , complying to  BS 7655, black Test voltage 50Hz, 1 min.
wire - wire
wire - armour


3500V
3500V
Armour single layer of galvanized steel wires complying to BS 1442 Temperature range
mobile
fixed

-5° C to +50° C  30° C to +70° C
Outer Sheath PVC compound type TM1 complying to BS 7655
Sheath colour orange Minimum bending radius approx. 15 x cable diameter

 

 

 

 

Type codes
PVC     insulation or sheath of            PVC
SWA    galvanized steel wires            armour

 

 

 

 

Cable core construction
Number of wires Centre First layer Second layer
4 4    
8 1 7  
12 2 9  
16 f 5 11
20 f 7 13

 

 