Interested in this product?

Send us a request and we will contact you

Our Certificates

Standart: BS 6346

Description: Cu conductors • PVC insulation • Armour St. wires • PVC sheath

Application:

These cables are used in power plants, industrial and switching installations, for street lighting, domestic power supply connections, in secondary distribution networks and other.These cables are preferentially used for underground application as well as for interior installation in room and cableducts and for outdoor and applications, for indoor installations, in the open air, underground and in water where greater mechanical protection an protection against accidental contact is required if damaged.

Features:

 

 

Cable construction

Technical data

Construction According to BS 6346 Conductor resistance at 20° C According to BS 6360 ( IEC 60228) class 1 or 2
Conductor Cu wires,class 1 or 2 according to BS 6360 (IEC 60228) Operating temperature max. +70° C continuous operation
Insulation PVC compound Short circuit temperature 250° C /5 s max./
Core identification according to BS 7655 Nominal voltage Uo/U 0.6/1 kV
Inner sheath filling compound Test voltage 3.5 kV   
Armour galvanized steel wires Temperature range
- laying and installing
- exploitation and storage
-5° C to +60° C
-25° C to +70° C
Sheath PVC compound Bending radius, min. approx. 6 x D cable
Color black Flame test IEC 332-1