Standart: FN KI 02.004/06 // SFS 5791/94
Description: Al conductors • XLPE insulation
Conductors with XLPE insulation for overhead lines, are designed for transfer and distribution of electrical power in overhead electrical networks with nominal voltage to Uo/U/Um 12/20/24 kV and frequency 50 Hz. The main characteristics of overhead lines with XLPE insulation overhead conductors are low susceptibility to operational failures when conductors strike against each other or when a tree is temporarily leaning on the line. Also the space in the terrain required for the line is narrower, specially in casse of parallel lines.
|
Construction data |
Technical data |
||
| Construction | According to FN KI 02.004 и SFS 5791/94 | Operating temperature | 90° C in operation |
| Conductor | - Al alloy conductor stranded compacted - steel reinforced Al stranded compacted or stranded type AC |
Short-circuit temperature | 250° C max. 5sec. |
| Nominal voltage 50Hz | Uo/U 12/20 kV (6/10kV) | ||
| Insulation | XLPE compaund | Highest system voltage Um not more than | 24 kV |
| Additional element | Longitudinal water blocking, may be provided by agreement between the manufacturer and the purchaser | Test voltage | 4kV / 5 min |
| Color | Black | Bending radius, min. | 10xD cable |
| Marking | SAH-20 - to FN КI 02 004 SAHv-20 -to FN КI 02 004 with longitudinal water blocking SАХ - по SFS 5791 /94 | Temperature of laying | no less than - 20° C recommended 15 ° C |