Interested in this product?

Send us a request and we will contact you

Our Certificates

Standart: IEC 60502-2, VDE 0276-620

Description: Cu / Al conductors • XLPE insulation • Cu screen with WB element• PE sheath

Application:

The three-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal water-blocking elements, are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20; 18/30 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer’s substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Features:

 

 

Cable construction

Technical data

Construction According to IEC 60502 and DIN VDE 0276-620 Conductor resistance According to BDS904 (IEC60228) class 2 and VDE 0295 class 2
Conductor Сu and Al stranded compacted, according to IEC 60228 class 2 and VDE 0295 class 2 Operating temperature 90° C continuous operation
Short circuit temperature 250° C ( 5 sec.)
Inner semi- conductive layer semi-conductive XLPE compound Overload temperature 130° C /100h per year max./
Insulation XLPE compound
Outer semi- conductive layer semi-conductive XLPE compound Nominal voltage Uo/U 6/10; 12/20; 18/30 kV
Highest system voltage Uo/U, no more than 6/10; 12/20; 18/30 kV
12kV; 24kV; 36kV
Test voltage
AC (») - 5 min
DC (=) - 15 min
6/10; 12/20; 18/30kV
21kV; 42kV; 63kV
67kV; 134kV; 201kV   
Water resisting element Layer of semi-conductive water absorbing tapes - discret Bending radius
15 x Dcable
Metal screen Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm Level of partial discharge at 2*Uo max. 5 pC / 2 pC
Water resisting element Layer of semi-conductive water absorbing tapes Temperature of laying no less than -5° C
Cable assembly Three insulated and screened phases with longitudinal water-blocking element are twisted in three core cable
Inner sheath Filling and inner sheath-PE - LDPE Temperature of exploitation -30° C to 50° C
 Sheath PE compound - HDPE Tests-longitudinal water-blocking according to IEC 60502-2/F or DIN VDE 0276-620
Color Black Force of strain in laying N max. Al cores - 30*n*S core
Cu cores - 50*n*S core,
-n-number of cores and -S-nominal cross section of cores in mm